5.2 ection 4.2.2.6.3)
5.2 section 4.2.2.6.4)
Digital
.3.8. Input Type (s
Select Frequency.
.3.9. Min Freq (
Min frequency = 0.100
Output 1 Setup (Over speed alarm)
.3.10. Source (section 4.2.4.1)
Navigate back to Digital Output 1 setup. Select Input A for source.
5.2
5.2 ion 4.2.4.2.1)
.2.4.2.2)
.4.1)
being used to ensure that the speed does not exceed 400 rpm.
t.
Digital
.3.11. Latch Mode (sect
Select Off
5.2.3.12. On / Off Delay (section 4
No delay is desired. Enter 0.00 for both.
5.2.3.13. Output Switching (section 4.2.4
Digital 1 is
Select EA (energize above)
Enter 4.000e+2 for the Alarm setpoint.
Enter 3.500e+2 for the Safe setpoin
Output 2 Setup
Navigate to Digital Output 2 setup. Make all constants the same except for Output
switching.
5.2.3.14.
he speed does not drop below 300
Select EB (energize below)
oint.
Relay Output 1 Setup (Failsafe Overspeed alarm)
Output Switching (section 4.2.4.4.2)
Digital 1 is being used to ensure that t
rpm.
Enter +3.000e+2 for the Alarm setpoint
Enter 3.500e+2 for the Safe setp
Relay Output 1 setup. Select Input A for source.
5.2.3.15. Source (section 4.2.4.1)
Navigate back to
5.2.3.16. Latch Mode (section 4.2.4.2.1)
Select Off
102
Vedere la pagina 113